HT-A Series Online UPS 1-3KVA

MAIN PARAMETERS

  • Input Voltage Range : 90-285Vac 1P2W+G.
  • Input Frequency : 40-70Hz (settable).
  • Output Voltage : 220Vac(1±2%) 1P2W+G.
  • Efficiency: ≥ 90% (Normal Mode).
  • Crest Factor :3 : 1
  • Transfer Time : 0 ms (Normal mode ← → Battery Mode).
Rating Index :
分类: , 标签: 品牌:

FEATURES
  • Advanced CPU digital control technology.
  • Active input power factor correction (PFC).
  • Frequency adaptive system.
  • Ultra wide input voltage range.
  • Output power factor is 0.9.
  • Ultra wide input frequency range.
  • Strong scalability.
  • Green and environmental protection.

Model HT-A 1K HT-A 1KL HT-A 2K HT-A 2KL HT-A 3K HT-A 3KL
Rated Power 1KVA/0.9KW 2KVA/1.8KW 3KVA/2.7KW
INPUT
Voltage Range 90-285Vac 1P2W+G
Working Frequency Range 40-70Hz (settable)
Input Power Factor ≥0.99
OUTPUT
Rated Voltage and Accuracy 220Vac(1±2%) 1P2W+G
Output Frequency 46-54Hz synchronize with mains power; 50Hz (Mains power between 40-46Hz and 54-60Hz ); 50Hz (Battery).
Rated Current 4.5A 9.1A 13.6A
Output Power Factor 0.9
Output Harmonic Wave ≤4%(Full R Load)
Crest Factor 3 : 1
Output Overload
(Normal Mode)
Overload pre-warning: 100%±2%<Load
Output warning: Convert to bypass mode and alarm after 30 mins, 102%±2%≤Load≤110%±2%
Output warning: Convert to bypass mode and alarm after 10 mins. 110%±2%< Load≤130%±2%
Output warning: Convert to bypass mode and alarm after 30s, 130%±2%< Load≤150%±2%
Convert to bypass mode and alarm after 200ms, Load >150%±2%
Transfer Time 0 ms (Normal mode ← → Battery Mode)
Efficiency ≥ 90% (Normal Mode)
BATTERY
Rated Voltage 24VDC 36VDC 48VDC 72VDC 72VDC 96VDC
Quantity 2 3 4 6 6 8
Charging Current 1A 5.5A 1A 5.5A 1A 5.5A
OTHER
Dimension (LxWxH) mm 280*144*230 280*144*230 280*144*230 400*144*230 425*190*328 400*144*230
Weight 7.8KG 4.2KG 13.3KG 6.4KG 23.4KG 6.5KG
Working Temperature 0℃〜40℃
Working Humidity 20%〜95% (non-condensing)
Noise ≤50dB