LT-A-33 Series Online UPS 10 – 200KVA

MAIN PARAMETERS

  • Input Voltage Range : 380 / 400 / 415 ; 165 ~ 280 ( Ph – N ) / 285 ~ 485 ( Ph – Ph ).
  • Input Frequency : 50 ± 5 ( ± 10% ) ; 60 ± 5 ( ± 10% ).
  • Output Voltage : 3 X 380VAC / 400VAC / 415VAC ( 3 Ph + N ) ±0.1%.
  • Output Frequency: Mains Mode : ( 50 / 60 ) ± 0.01 Hz ; Battery Mode : ( 50 / 60 ) ± 0.01 Hz.
  • THD:Resistive Load : ≤ 2% ; Non – Linear Load : ≤ 4%.
  • Transfer Time : 0 ms (Normal mode ← → Battery Mode).
Rating Index :
分类: , 标签: 品牌:

FEATURES
  • Optional 7 " touch LCD.
  • Online double-conversionDSP technology guarantees high reliability.
  • True galvanic isolation transformer design.
  • Control designed to withstand all kinds of loads.
  • Intelligent battery management to prolong battery lifecycle.
  • Redundant fan design and independent ventilation enhance durable operation under harsh environment.
  • Adiustable battery numbers.
  • Accept dual-mains input.
  • Parallel operation with up to 4 units (option).
  • Variety of communication options available.
  • Reverse phase frequency operation and supportsnon-neutral input.
APPLICATION
  • Telecommunication / Electric power and energy sources / Finance / Securities Hospital devices / School,Aviation / Airport / Taxation and Industrialequipment.

MODEL LT-A-33 10K LT-A-33 20K LT-A-33 30K LT-A-33 40K LT-A-33 60K LT-A-33 80K LT-A-33 100K LT-A-33 120K LT-A-33 160K LT-A-33 200K
Rated Capacity 10KVA / 8KW 20KVA / 16KW 30KVA / 24KW 40KVA / 32KW 60KVA / 48KW 80KVA / 64KW 10KVA / 80KW 120KVA / 96KW 160KVA / 128KW 200KVA / 160KW
MAIN CIRCUIT INPUT DATA
Input Voltage Range (Vac) 380 / 400 / 415 ; 165 ~ 280 ( Ph – N ) / 285 ~ 485 ( Ph – Ph )
Number Of Phases 3 Phase + N + PE
Input Frequency Range (Hz) 50 ± 5 ( ± 10% ) ; 60 ± 5 ( ± 10% )
Input Power Factor ≥ 0.7 ( Non-Filter ) ; ≥ 0.97 ( With Filter )
Rectification Technology Silicon Controlled Rectifier (SCR)
THDI < 50% ( Non-Filter ) ; < 15% ( With Filter )
BYPASS INPUT DATA
Input Voltage Range (Vac) 176 ~ 264 ( Ph – N ) / 304 ~ 456 ( Ph – Ph )
Number Of Phases 3 Phase + N + PE
Frequency Tracking Range (Hz) 50 ± 5 ( ± 10% ) ; 60 ± 5 ( ± 10% )
Generator Connection Support
Overload Capacity 150%~180% 1h~300s ; > 180% 300s
OUTPUT DATA
Output Voltage (Vac) 3 X 380VAC / 400VAC / 415VAC ( 3 Ph + N )
Output Voltage Regulation Accuracy ± 1%
Output Active Power 0.8
Output Frequency (Hz) Mains Mode : ( 50 / 60 ) ± 0.01 Hz ; Battery Mode : ( 50 / 60 ) ± 0.01 Hz
Output waveform Pure Sine Wave
THD Resistive Load : ≤ 2% ; Non – Linear Load : ≤ 4%
Mains-To-Battery Conversion Time 0 ms
Efficiency (%) Linear Mode: 89% ; Battery Mode: 90% Linear Mode: 90% ; Battery Mode: 91% Linear Mode: 91% ; Battery Mode: 92%
Overload Capacity ≤ 110% : 60 Minutes; ≤ 125% : 10 Minutes; ≤ 150% : 1 Minutes; > 150% : 200 ms
RECTIFICATION
Type 6 Pulses
Rated Output Voltage 384 Vdc
Charge Voltage 395 Vdc ~ 435 Vdc (Adjustable)
BATTERY
Type Sealed Valve – regulated Lead – acid Battery (VRLA)
Battery Voltage (Vdc) 12Vdc * 32 Pcs ( 29~32 Pcs Adjistable ) ; 348 / 360 / 372 / 384 Vdc
Charging Capability Max. = Capacity (KW) / Bat. Voltage (Real Time) Max. 40A ; 5A @ Full Load
* The max. current will never be higher than 40A
COMMUNICATION AND MANAGEMENT
Communication Function RS232, USB, RS485, Dry Contacts; One Slot For Communication Card, Can Accommodate SNMP Card.
Control Panel 3.5 – Inch LCD Screen; 7 – Inch Full – Color Touch Screen (Optional)
Warning Function Output Overload, Abnormal Mains Power Supply, UPS Failure, Low Battery Voltage, Supports Historical Record Querying
Protection Function Output Short – Circuit, Output Overload, Over – Temperature, Low Battery Voltage, Output Over – Voltage And Under – Voltage, Fan Failure, Lightning Protection
OTHER FUNCTIONS
ECO Mode / EPO Function Support
Power-Up Function Support ( * )
Synchronous Controller Optional ( * )
Type VFI-SS-111
Battery Charging Standard DIN 41773
Parallel Number 4 Pcs
ENVIRONMENTAL CONDITIONS
Operating Temperature (℃) 0 ~ 55°C
Storage Temperature (℃) -25 ~ 55°C ( Excluding Battery )
Relative Humidity < 95% ( Non – Condensing )
Operating Altitude 0 To 1500M At 100% Load
Audio Noise 70dB At 100% Load
PROTECTION
Protection Level IP20
Three-Proof Coating / Dust Screen Support
PHYSICAL CHARACTERISTICS
Dimensions (W × D × H) (mm) 405 x 656 x 817 405 x 656 x 941 432 x 821 x 1159 554 x 975 x 1286 635 x 975 x 1326 705 x 1051 x 1646
Weight (Kg) 118 145 193 278 365 471 573 650 760 790
EXECUTIVE STANDARDS
Safety Regulations IEC/EN 62040-1-1, IEC/EN 60950-1
Electromagnetic Compatibility IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8, EN5502
Performance Testing IEC 62040-3
Environmental Requirements IEC 62040-4
Labeling CE
* indicates that this function can be achieved. Specifications are subject to change without prior notice.